2907081 Uninterruptible power supply – QUINT4-UPS/24DC/24DC/40/EC
-
Input Data
Input voltage | 24 V DC |
Input voltage range | 18 V DC … 30 V DC |
18 V DC … 32 V DC | |
Electric strength, max. | 35 V DC |
Internal input fuse | no |
Voltage type of supply voltage | DC |
Inrush current | ≤ 9 A (≤ 4 ms) |
Reverse polarity protection | yes |
Fixed backup threshold | 22 V DC |
Dynamic activation threshold | > 1 V / 100 ms |
Switch-on time | max. 3 s |
Switch-on time during battery operation (Bat.-Start) | 8 s |
Voltage drop, input/output | 0.5 V DC |
Current consumption IN (UN, IOUT = IN, Icharge = 0) | 40.1 A |
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max) | 51.2 A |
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0) | 105 mA |
Current consumption Icharge (UN, IOUT = 0, Icharge = max) | 6.1 A |
Power consumption PN (UN, IOUT = IN, Icharge = 0) | 967 W |
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max) | 1122 W |
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0) | 2.6 W |
Power consumption Pcharge (UN, IOUT = 0, Icharge = max) | 148 W |
-
Input Connection Data
Connection method | Screw connection |
Conductor cross section solid | 0.5 mm² … 16 mm² |
Conductor cross section flexible | 0.5 mm² … 16 mm² |
Flexible conductor cross-section with ferrule | 0.5 mm² … 16 mm² |
Conductor cross section AWG | 8 … 6 |
Stripping length | 10 mm |
Torque | 1.2 Nm … 1.5 Nm |
-
Output Data
Efficiency | typ. 97 % |
Number of outputs | 1 |
Nominal output current (IN) | 40 A (-25 °C … 50 °C) |
Short-circuit-proof | yes |
No-load proof | yes |
Switch-over time | 0 ms |
Output current limit | In mains mode according to connected upstream current limiting device |
> 45 A (Battery operation) | |
Power dissipation | 2.8 W (Mains operation) |
13 W (Mains operation) | |
3.51 W (Battery operation) | |
16.4 W (Battery operation) | |
UPS connection in parallel | no |
UPS connection in series | no |
Energy storage device connection in parallel | Yes, 5 (observe line protection) |
Energy storage device connection in series | no |
-
Output Connection Data
Connection method | Screw connection |
Conductor cross section solid | 0.5 mm² … 16 mm² |
Conductor cross section flexible | 0.5 mm² … 16 mm² |
Flexible conductor cross-section with ferrule | 0.5 mm² … 16 mm² |
Conductor cross section AWG | 8 … 6 |
Stripping length | 10 mm |
Torque | 1.2 Nm … 1.5 Nm |
Additional information
Approval | EAC UL Listed cUL Listed DNV GL cUL Listed UL Listed |
---|---|
Input voltage | 24 V DC |
Buffer time | 45 min. (38 Ah) |
Main operation output voltage | 18 V DC … 30 V DC |
Battery operation output voltage | 19 V DC … 32 V DC |
-